Standard System LA/DL/LL Series
Keywords:
Standard System LA/DL/LL Series
Category:
Product Description
The standard LA/DA/LL series components are used to cool or heat the coolant flowing through a liquid heat exchanger. This heat exchanger is specifically designed for use in circulating cooling systems and requires a pump and associated piping to complete the liquid circuit.
On the cooling side, heat is absorbed by a heat exchanger, while a custom-designed thermoelectric cooler pumps this heat to a paired heat exchanger on the heat dissipation side. The heat dissipation side can employ:
> Convection mode: (Liquid to Air)
> Conduction method: (Direct to Liquid)
> or via liquid-to-liquid transfer: (Liquid to Liquid)
To enhance heat transfer, turbulators have been inserted into the liquid channels of the heat exchanger. However, for applications involving higher liquid flow rates, these turbulators can be removed to reduce pressure drop.
Usually used for
► Sample storage room for medical and analytical instruments
► Point Cooling for Laser Systems in the Industrial and Telecommunications Markets
► Cooling of Sensitive Optoelectronic Devices in the Industrial and Telecommunications Markets
Liquid-to-Air Series
| Model | QC Max (W) |
Current (A) | Voltage (V) | Fan position | Input power (W) | COP | Operating temperature (℃) | L × W × H (mm) |
| LA-024-12 | 24 | 2.4 | 12 | Hot side | 29 | 0.83 | -10 ~ 52 | 80 x 60 x 81 |
| LA-045-12 | 45 | 4.1 | 12 | 49 | 0.92 | 160 x 122 x 91 | ||
| LA-075-24 | 75 | 3.7 | 24 | 89 | 0.84 | 230 x 122 x 91 | ||
| LA-115-24 | 115 | 5.8 | 24 | 139 | 0.83 | 300 x 152 x 98 | ||
| LA-160-24 | 160 | 7.4 | 24 | 178 | 0.90 | 300 x 152 x 105 | ||
| LA-200-24 | 200 | 9.5 | 24 | 228 | 0.88 | 199 x 167 x 167 | ||
| LA-300-12 | 300 | 33.3 | 12 | 400 | 0.75 | 297 x 160 x 165 | ||
| LA-300-24 | 300 | 15 | 24 | 360 | 0.83 | 297 x 160 x 165 | ||
| LA-400-12 | 380 | 38 | 12 | 456 | 0.83 | 297 x 160 x 165 | ||
| LA-400-24 | 400 | 20 | 24 | 480 | 0.83 | 297 x 160 x 165 |
Flat Surface Liquid Series
| Model | QC Max (W) |
Current (A) | Voltage (V) | Input power (W) | COP | Operating temperature (℃) | Weight (Kg) | L × W × H (mm) |
| DL-060-12 | 60 | 4.7 | 12 | 50 | 1.20 | -10 ~ 63 | 0.40 | 100 x 60 x 39 |
| DL-120-24 | 120 | 4.2 | 24 | 101 | 1.19 | 0.68 | 140 x 60 x 39 | |
| DL-210-24 | 210 | 8.1 | 24 | 194 | 1.08 | 1.30 | 240 x 60 x 39 |
Liquid-to-Liquid Series
| Model | QC Max (W) |
Current (A) | Voltage (V) | Input power (W) | COP | Operating temperature (℃) | Weight (Kg) | L × W × H (mm) |
| LL-060-12 | 60 | 4.2 | 12 | 50 | 1.20 | -10 ~ 63 | 0.50 | 100 x 60 x 44 |
| LL-120-24 | 120 | 4.2 | 24 | 101 | 1.19 | -10 ~ 63 | 0.82 | 140 x 60 x 44 |
| LL-210-24 | 210 | 8.1 | 24 | 194 | 1.08 | -10 ~ 63 | 1.40 | 240 x 60 x 44 |